Series 100 Fire Damper Model BM

Square/Rectangular spigot, Galvanised steel frame and stainless steel blades, Blades out of airstream

The need to protect people and buildings from the spread of fire is of paramount importance in any building, and one of the best ways for fire to spread quickly is through ductwork.

This is why high quality dependable fire dampers are needed. Having satisfied both four and six hour tests to BS and ISO standards, HVC S100BM Fire Dampers are some of the best available. You cannot put a price on peace of mind.

View the full S100BM PDF
Send the S100BM PDF via email

Application

  • Endurance Tested to BS476-20 by Warrington F.R.C. for 6 hours with guaranteed closure in both vertical and horizontal planes
  • Tested to the latest BS1366-2 (ISO10294-1) for the maximum 4 hours at 300 Pascals by the Building Research Establishment
  • Square/Rectangular Spigot
  • Galvanised steel frame and stainless steel blades
  • Blades out of airstream

The design of S100BM Fire Dampers means they are suitable for use in high velocity airstreams thanks to their blade pack being stowed in an extended compartment during normal operation.

Unlike its fully galvanised S100BG cousin, S100BM Fire Dampers have a fully stainless steel blade pack, made from either 430, 316 or 304 grade stainless steel, creating a damper more resistant to damage through corrosion. However, should full protection against the effects of corrosion be required, please view our S100BS fully stainless steel Fire Dampers.

Description

With their stainless steel blades, S100BM Fire Dampers already have corrosion resisting properties far exceeding those of standard fire dampers. Fire testing however is still required, and the whole range of HVC S100 Fire Dampers have been tested to BS1366-2 (ISO10294-1) and BS476-20, for certified performance. In addition to fire testing, leakage tests in the form of DW144 have also been carried out and passed.

In the test house though conditions were controlled and clean, dampers were brand new and the effects of years sitting in a duct had not been evaluated. That is why HVC S100 Fire Dampers have been subjected to dust build up, cycling and corrosion tests to ensure operation, even after years of exposure to potentially operation hindering conditions

Require remote operation or remote blade position indication with your S100BM Fire Damper, no problem. We can factory fit a wide range of options to your fire damper to enhance functionality right out of the box. See the options tab above to find out more.

Specification

S100BM
Application Fire Damper
Recommended Use Fire Protection
Overall Dimension Varies Based on Size, See PDF
Overall Depth 70mm, 140mm Including Spigots
Standard Finish Silver
Material Galvanised Steel Frame, Stainless Steel Blades
Blade Type Curtain
Standard Control Option Fusible Link (72°C)

Gallery


Options


Visual Position Indicator

Allows the blade pack position to be observed from outside ductwork

Microswitch

Creates an electrical circuit when the blade pack closes, informing systems that a fire may have caused the damper to close

Solenoid

Releases the fusible link when power is gained, closing the damper remotely

Electromagnet

Releases the fusible link when power is lost, enabling remote damper operation

Fusible Link

As an alternative to the standard 72°C rating, 96°C, 145°C and 183°C are available on request

Related


Greater Resistance to Corrosion

Adding a stainless steel frame, S100AS Fire Dampers build on S100AM Fire Dampers, bringing the maximum level of corrosion resistance

HEVAC or Plasterboard Frame Needed?

With the choice of either, S100AMH Fire Dampers bring the additional benefits of a builderswork frame

Circular Spigot

S100AM Fire Dampers are designed for square ducting systems. For circular systems S100CM Fire Dampers are required