sales@h-v-c.com | +44 (0)1384 376555
product browser

Series 100 Fire Damper Model CS

Circular spigot, All stainless steel construction, Blades out of airstream

Protecting buildings and lives, and conforming with building regulations means that high quality fire dampers like our S100CS all stainless steel fire damper are essential.

This high quality is not just an opinion though, all HVC S100 Fire Dampers are certified to both British and International standards. In a fire you need the best protection available.

View the full S100CS PDF
Send the S100CS PDF via email

Application

  • Endurance Tested to BS476-20 by Warrington F.R.C. for 6 hours with guaranteed closure in both vertical and horizontal planes
  • Tested to the latest BS1366-2 (ISO10294-1) for the maximum 4 hours at 300 Pascals by the Building Research Establishment
  • Circular spigot
  • All stainless steel construction
  • Blades out of airstream

With both blades and frame made from stainless steel, these fire dampers have an exceptional resistance to corrosion, making them suitable for areas like swimming pools or offshore applications. Thanks to their blades being housed entirely out of the airstream during normal operation, S100CS Fire Dampers can be used in any velocity airstream.

Designed to suit spiral and flexible ducting, S100CS Fire Dampers have a stainless steel circular spigot enabling connection to spiral and flexible circular ducting.

Description

Testing for all S100 Fire Dampers includes BS1366-2 (ISO10294-1), a four hour fire test at an extreme 300Pa of pressure. As well as BS476-20, a more endurance focused test lasting a full six hours at ambient pressure. In every case S100 Fire Dampers satisfied the requirements.

Conditions inside ductwork however are rarely clean, and normal maintenance routines call for damper operation to be checked, requiring the damper to be closed; unlike in testing where dampers are clean and brand new. So HVC S100 Fire Dampers have undergone reliability, spring cycling and dust loading tests to guarantee operation.

A fire damper needs to suit its environment perfectly to be truly effective. That is why on top of the choices offered by different models, we offer an extensive range of options including visual position indicators, micro switches and solenoids. All extra equipment is factory fitted for ease of installation.

Specification

S100CS
Application Fire Damper
Recommended Use Fire Protection
Overall Dimension Varies Based on Size, See PDF
Overall Depth 70mm, 160mm Including Spigots
Standard Finish Silver
Material Stainless Steel
Blade Type Curtain
Standard Control Option Fusible Link (72°C)

Gallery


Options


Stainless Grades

As standard Grade 430 is used to manufacture all stainless steel fire dampers, however 316 and 304 can be specified for even greater corrosion resistance

Visual Position Indicator

Allows the blade pack position to be observed from outside ductwork

Microswitch

Creates an electrical circuit when the blade pack closes, informing systems that a fire may have caused the damper to close

Solenoid

Releases the fusible link when power is gained, closing the damper remotely

Electromagnet

Releases the fusible link when power is lost, enabling remote damper operation

Fusible Link

As an alternative to the standard 72°C rating, 96°C, 145°C and 183°C are available on request

Related


Don't Need Fully Stainless?

Perhaps you don't need so much corrosion resistance, S100CM Fire Dampers use a galvanised not stainless frame

HEVAC or Plasterboard Frame Needed?

With the choice of either, S100CSH Fire Dampers bring the additional benefits of a builderswork frame

Square/Rectangular Spigot

S100CS Fire Dampers are designed for circular ducting systems. For square systems S100BS Fire Dampers are required

Flat Oval Spigot

Perhaps you need a flat oval spigot not circular. S100DS Fire Dampers will be of more use to you