sales@h-v-c.com | +44 (0)1384 376555
product browser

Series 100 Fire Damper Model CSH

Circular spigot, All stainless steel construction, Blades out of airstream, With installation frame

The need to ventilate not only means occupant comfort is improved, but also creates pathways for fire to travel through, enabling a localised fire to become widespread in a short space of time.

Just like you would use a fire door to keep flames within one room, so you should use fire dampers to prevent the spread through ducting. It goes without saying that such a severe threat demands the highest quality equipment to tackle it.

View the full S100CSH PDF
Send the S100CSH PDF via email

Application

  • Endurance Tested to BS476-20 by Warrington F.R.C. for 6 hours with guaranteed closure in both vertical and horizontal planes
  • Tested to the latest BS1366-2 (ISO10294-1) for the maximum 4 hours at 300 Pascals by the Building Research Establishment
  • Circular spigot
  • All stainless steel construction
  • With installation frame
  • Blades out of airstream

The H in S100CSH denotes that this fire damper has a factory fitted installation frame. These frames are designed to integrate the damper into the surrounding building work, and, in the event of a fire aid the partition in maintaining its integrity and so helping to prevent the spread of fire.

The S also denotes a full stainless steel construction, with the choice of 430, 316 or 304 grade stainless. This makes S100CSH Fire Dampers highly resistant to corrosion by substances like salt or chlorine.

Description

In addition to a full stainless steel construction, S100CSH Fire Dampers come certified to a range of appropriate fire tests, designed to confirm the excellent performance of this range of fire dampers. All S100 Fire Dampers have been tested to, and successfully passed BS1366-2 (ISO10294-1) and BS476-20 fire tests.

The dampers which obtained the fire ratings though had not been sat in ductwork for years. Obviously this needs to be simulated and then tested to inspire real confidence in your dampers. So, the effects of dust loading, cycling and salt spray tests have all been simulated on S100 Fire Dampers. In all cases the tested dampers were observed to close and latch perfectly afterwards.

Need remote operation? Or perhaps resettable links for easy maintenance? No problem. With the range of factory fitted options shown in the options tab above, you can make your fire dampers suit your needs perfectly.

Specification

S100CSH
Application Fire Damper
Recommended Use Fire Protection
Overall Dimension Varies Based on Size, See PDF
Overall Depth 80mm, 160mm Including Spigots
Standard Frame HEVAC, Plasterboard Optional
Standard Finish Silver
Material Stainless Steel (Builders Frame Galvanised Steel)
Blade Type Curtain
Standard Control Option Fusible Link (72°C)

Gallery


Options


HEVAC or Plasterboard

HEVAC and Plasterboard fixing frames are available for fitment to all S100 Fire Dampers

Stainless Grades

As standard Grade 430 is used to manufacture all stainless steel fire dampers, however 316 and 304 can be specified for even greater corrosion resistance

Visual Position Indicator

Allows the blade pack position to be observed from outside ductwork

Microswitch

Creates an electrical circuit when the blade pack closes, informing systems that a fire may have caused the damper to close

Solenoid

Releases the fusible link when power is gained, closing the damper remotely

Electromagnet

Releases the fusible link when power is lost, enabling remote damper operation

Fusible Link

As an alternative to the standard 72°C rating, 96°C, 145°C and 183°C are available on request

Related


Fully Stainless Too Much?

If the superb corrosion resistance of S100ASH Fire Dampers is not needed, S100CMH Fire Dampers with their galvanised steel frame are more suitable

Don't Need an Installation Frame?

If a HEVAC or Plasterboard fixing frame is not required, S100CS Fire Dampers are therefore more suitable

Square/Rectangular Spigot

S100CMH Fire Dampers are designed for circular ducting systems. For square systems S100BSH Fire Dampers are required

Flat Oval Spigot

Perhaps you need a flat oval spigot not circular. S100DSH Fire Dampers will be of more use to you

Stock Information