Series 100 Fire Damper Model DGH

Flat oval spigot, All galvanised steel construction, Blades out of airstream, With installation frame

Fire can never be completely ruled out anywhere, and with the capability to destroy buildings and kill occupants, it is a threat which needs to be countered carefully.

Part of countering fire effectively is using certified fire dampers like our S100DGH. Able to stop the spread of fire for up to six hours buys invaluable time for fire fighters to come in and combat the fire while it is still localised.

View the full S100DGH PDF
Send the S100DGH PDF via email

Application

  • Endurance Tested to BS476-20 by Warrington F.R.C. for 6 hours with guaranteed closure in both vertical and horizontal planes
  • Tested to the latest BS1366-2 (ISO10294-1) for the maximum 4 hours at 300 Pascals by the Building Research Establishment
  • Flat oval spigot
  • All galvanised steel construction
  • With installation frame
  • Blades out of airstream

Delivered factory fitted with either a HEVAC or plasterboard fixing frame, S100DGH Fire Dampers are designed to become an integral part of the fire partition they are placed in. The frame strengthens both the wall and the damper, helping to resist the extreme distortion that may occur during a sever fire.

In HVC Fire Damper codes, "G" denotes a fully galvanised steel construction. These dampers are therefore not intended for use in corrosive atmospheres, where the risk of the blade pack becoming fully seized is a real danger. The flat oval spigot makes fitment into flat oval ducting quick and effective.

Description

With BS1366-2 (ISO10294-1) and BS476-20 all satisfied across the entire S100 range of fire dampers, you can be certain of excellent performance even in the most extreme fires with your S100DGH Fire Damper. In addition to fire tests, all fire dampers also satisfy DW144 leakage tests.

S100 Fire Dampers have also undergone reliability, spring cycling and dust loading tests, simulating the effects of years of being sat inside a duct. All tests resulted in dampers being able to close effectively when subjected to flame.

With our wide range of options available to suit your new S100DGH Fire Damper, we are able to make your damper suit whatever requirement you have.

Specification

S100DGH
Application Fire Damper
Recommended Use Fire Protection
Overall Dimension Varies Based on Size, See PDF
Overall Depth 80mm, 160mm Including Spigots
Standard Frame HEVAC, Plasterboard Optional
Standard Finish Silver
Material Galvanised Steel
Blade Type Curtain
Standard Control Option Fusible Link (72°C)

Gallery


Options


HEVAC or Plasterboard

HEVAC and Plasterboard fixing frames are available for fitment to all S100 Fire Dampers

Visual Position Indicator

Allows the blade pack position to be observed from outside ductwork

Microswitch

Creates an electrical circuit when the blade pack closes, informing systems that a fire may have caused the damper to close

Solenoid

Releases the fusible link when power is gained, closing the damper remotely

Electromagnet

Releases the fusible link when power is lost, enabling remote damper operation

Fusible Link

As an alternative to the standard 72°C rating, 96°C, 145°C and 183°C are available on request

Related


Don't Need an Installation Frame?

You may not need a HEVAC or plasterboard fixing frame. S100DG Fire Dampers are therefore more suitable

Corrosive Substances Present?

If exposure to substances like salt or chlorine is likely, S100DMH Fire Dampers with their stainless steel blade pack are more suitable

Square/Rectangular Spigot

S100DGH Fire Dampers are designed for flat oval ducting systems. For square systems S100BGH Fire Dampers are required

Circular Spigot

Perhaps you need a circular spigot instead of flat oval? S100CGH Fire Dampers will be of more use to you